Sign In | Join Free | My himfr.com
Home > Fire Testing Equipment >

Gypsum Board Flammability stability tester Fire Resistance Testing Machine

    Buy cheap Gypsum Board Flammability stability tester Fire Resistance Testing Machine from wholesalers
     
    Buy cheap Gypsum Board Flammability stability tester Fire Resistance Testing Machine from wholesalers
    • Buy cheap Gypsum Board Flammability stability tester Fire Resistance Testing Machine from wholesalers

    Gypsum Board Flammability stability tester Fire Resistance Testing Machine

    Ask Lasest Price
    Brand Name : SKYLINE
    Model Number : SL-SGF01
    Certification : CE
    Price : negoitable
    Payment Terms : T/T
    Supply Ability : 1 unit/Month
    Delivery Time : 15 working days
    • Product Details
    • Company Profile

    Gypsum Board Flammability stability tester Fire Resistance Testing Machine

    Application


    It is used for measuring plasterboard stability in case of fire, and can also be applied to other building materials, decoration materials, and fire prevention performance measurement.


    Test Introduction


    The test involves drilling and processing under prescribed conditions. The sample is suspended between two fire nozzles with a support rod, making the fire nozzles perpendicular to the surface of the sample. Liquefied petroleum gas is used as the heat source to supply gas to the two burners of the fire stability tester. The distance between the burner nozzle and the plate surface is 30mm.

    A load is suspended at the lower end of the specimen as per the standard and the burner is ignited. The temperature is measured at a distance of 5mm from the plate surface using a thermocouple. During the initial stage of the test, any carbonized protective paper that has fallen onto the thermocouple should be removed without shaking the sample.

    Through adjustment, the temperature is controlled at (800±30)℃ within 3 minutes and maintained at this temperature throughout the test. Timing begins from the moment the specimen is exposed to fire until it breaks and fails. The time taken for each specimen to be burned off is recorded, and the minimum value among five specimens is taken as the fire stability of this group of specimens, accurate to 1 minute.


    Test Parameter


    Supply voltage: 220W ± 10%, 50HZ
    Power: 180W
    Ignition: Automatic ignition
    Thermocouple: Double thermocouple temperature measurement
    Timer: Temperature and time digital display
    Burner: Double burner, for Φ 9.5 mm ± 0.5 mm, inner diameter about 100 mm long, with air conditioning nut 10 mm, spray fire head (40 ± 1) mm in diameter, spray fire flame hole diameter (2.5 ± 0.1) mm
    Fire Height: 20 mm - 100mm
    Burning duration: Adjustable applying time and duration of a burning flame in 0 ~ 99 minutes, 99 seconds range adjustment test process automatic control
    The style break fall automatically records the combustion time
    Source: Test flames of air using liquefied gas or oil gas (suggest choosing better quality gas)
    Flow adjusting range: 100 ~ 1000 ml/Min
    Timing precision (resolution): 0.1 s
    Test temperature: 800-30℃, maximum temperature 900℃, precision grade 1 time temperature stability: < 3 min (800 ± 30℃)
    Specimen: 300 mm (length) x 50 mm (width), with holes on both sides at 25 mm distance
    Hanging load respectively: 7, 10, 12, 15, 17, 20 N (0.75 ~ 2.5 kg conversion unit suspended load)
    Dimensions: 700 (width) x 300 (deep) x 600 (height) mm (800 mm outer)
    Packing size: 800 (width) x 420 (deep) x 700 (height) mm


    Test Standard


    GB/T9775-2008(ISO6308:1980)


    Product Specification


    AttributeValue
    Power220V±10%50Hz/180W
    LightingAutoignition
    Timing accuracy (resolution)0.1 seconds
    Temperature stabilization time<3 minutes (800±30) ℃
    The flow regulation range100 to 1000 ml /Min
    Flame length20mm to 100mm(Adjustable)

    Installation Specifications


    PlaceDimension700(W)×300(D)×600(H)mm
    WeightAbout 30 kg
    Test tableRequire no less than 1 meter height and a width of no less than 0.75 meters
    Power SupplyVoltage220V±10%, 50HZ
    Power180W
    Water SourceNA
    Air SourceLiquefied petroleum gas (recommended to choose gas with better quality)
    PollutantsDust
    Ventilation requirementsThe equipment needs to be placed in a fume hood or collected for flue gas and connected to the flue gas treatment and purification system
    Other test requirementsGas cylinder matching pressure reducing valve (capable of adjusting to 0.3 megapascals)